Our CX2000 is a fully-featured conductivity controller and 4-20mA transmitter for reading contacting conductivity sensors and programming process control. Set points are easily selected for 2 relay outputs and 1 wash control. Sensor calibration is simple with preset standards. The large LCD display features auto-sense back-light technology for use in all environments, including cooling tower controller applications.
Note: CX2000 Conductivity Controller and 4-20mA transmitter is compatible with sensors with tinned lead connectors and either 30k NTC or Pt1000Ω RTD temperature compensation.
CA Residents: Prop 65 WARNING(S)
Measuring Range:
Calibration Mode: Automatic with built-in standard solutions manual cell constant adjustment
Cell Constants: 0.01, 0.05, 0.1, 0.5, 10/cm fixed or freely selectable 0.0080 – 19.99/cm
Analog Output 1: Isolated DC 0/4 -20mA, corresponding to conductivity or resistivity. Max load 500 Ω.
Analog Output 2: Isolated DC 0/4 -20mA, corresponding to temperature output. Max load 500 Ω.
Set-Points: Contact: 240V AC, 5A max
Activate: setpoints Hi/Low, Hi/Hi, Low/Low, ON/OFF
Enclosure: NEMA 4X IP65, with push-button control pad. HWD: 96 mm (3.77”) x 132 mm (5.20”), 1/4 DIN
Panel Cut-Out: 93mm (3.66”) x 93mm (3.66”)
Weight: approx. 0.50kg (1.1lb)
Mounting Options: Panel or Wall Mount
Ambient Temperature: 0 ° C to 50 ° C
Storage Temperature: -10 ° C to 70 ° C
Temperature Compensation: NTC 30K or Pt1000 RTD with automatic compensation or manual
Temperature Coefficient: Linear comp 0.00-40.00%, Non-linear comp for natural waters
Power Requirement: 100-240V AC +/- 10%, 5W max, 50/60 H
| Weight | 2.40 lbs |
|---|---|
| Dimensions | 11 × 10.5 × 7 in |
| Select Outputs | 2x 4-20mA, 1x 4-20mA + 1x MODBUS |
Our CX2000 is a fully-featured conductivity controller and 4-20mA transmitter for reading contacting conductivity sensors and programming process control. Set points are easily selected for 2 relay outputs and 1 wash control. Sensor calibration is simple with preset standards. The large LCD display features auto-sense back-light technology for use in all environments, including cooling tower controller applications.
Note: Transmitter is only compatible with sensors with tinned leads and either 30k NTC or Pt1000Ω RTD temperature compensation.