TX2000 - Intelligenter pH- und ORP-Sender/Regler

TX2000 – Intelligenter pH- und ORP-Sender/Regler

TX2000
Der TX2000 ist ein intelligenter Sender/Regler zur Erfassung von pH‑ und ORP‑Sensoren sowie zur programmierbaren Prozesssteuerung. Das große LCD zeigt pH/ORP‑Werte gleichzeitig mit der Temperatur an; kompatibel mit allen Sensorex Kombinations‑pH‑ und ORP‑Sensoren und für Schalttafel‑ oder Wandmontage geeignet.
Beeilen Sie sich! 100 noch Artikel auf Lager.
1.414 €
Bruttopreis
Menge

Our TX2000 is an intelligent pH and ORP transmitter/controller for reading pH and ORP sensors and programmable process controls. The large LCD screen displays the pH/ORP value simultaneously with the temperature. This transmitter is compatible with all Sensorex combination-style pH and ORP sensors. Versatile mounting options for panel or wall mounting.

  • Reliable pH/ORP monitoring and process control: Proven technology for pH/ORP monitoring and process control with sample averaging for increased stability
  • Simple sensor calibration: Large display shows sensor data and aids in the calibration process
  • High-accuracy measurements: Solution ground input eliminates measurement errors caused by reference ground potentials
  • Compatible with a wide variety of sensors: For use with all Sensorex combination-style pH/ORP sensors
  • One year limited warranty: We stand behind all our products with the Sensorex Guarantee

Note: Transmitter is only compatible with sensors with tinned leads.

CA ResidentsProp 65 WARNING(S)



  • Measurement Range: 

    • pH: -2.00 to 16.00pH, 0.01 pH resolution
    • ORP/mV: -1999mV to 1999mV, 1mV resolution, +/- 2mV accuracy
    • Temperature : -20 °C to 110 °C , 0.1 °C resolution, 0.2 °C accuracy

    Calibration Mode: Any Tech & NIST or custom buffers up to 5 points

    Enclosure: NEMA 4X IP65, with push-button control pad. HWD: 96 mm (3.78″) x 96 mm (3.78″) x 132mm (5.20″), 1/4 DIN

    Panel Cut-Out: 93mm (3.66″) x 93mm (3.66″)

    Display: Large LCD, auto-sense backlight, text, chart or trace mode

    Analog Output 1: 0/4 -20mA, corresponding to pH or ORP output. Max load 500 Ω.

    Analog Output 2: 0/4 -20mA, corresponding to temperature output. Max load 500 Ω

    Voltage Output: DC +/- 12V, 1W max

    Alarm/Control Relays: Contact: 240V AC, 5A max Activate: 2 setpoints Hi/Low, On/Off

    Wash Setting: Contact: 240V AC, 30V DC 5.0A max On: 0-9999 seconds /Off: 0-9999 hours

    Mounting Options: Panel or wall mounting

    Ambient Operating Temperature: 0° C to 50° C

    Ambient Humidity: 0 to 95%, non-condensing

    Temperature Compensation: NTC 30K or Pt1000Ω RTD with automatic compensation or manual

    Power Requirement: 100-240V AC +/- 10%, 9W max., 50/60 Hz

    Warranty: One year limited warranty

    Weight: Approx. 1.10lb (0.50kg)

    Certifications: CE



Weight2.27 lbs
Dimensions11 × 10.5 × 7 in

Our TX2000 is an intelligent transmitter/controller for reading pH and ORP sensors and programmable process control. The large LCD display shows pH/ORP value simultaneously with temperature. Compatible with all Sensorex combination-style pH and ORP sensors. Versatile mounting options for panel or wall mounting.

  • Reliable pH/ORP monitoring and process control
  • Simple sensor calibration
  • High-accuracy measurements
  • Compatible with all Sensorex combination-style pH/ORP sensors
  • One year limited warranty

Note: Transmitter is only compatible with sensors with tinned leads.

: TX2000
: 100 Artikel
Beeilen Sie sich! 100 noch Artikel auf Lager.

Technische Daten

Anwendungen
Regler und Sender, Hydroponik und Landwirtschaft, ORP, pH
Umgebungsfeuchte
0–95 %, nicht kondensierend
Zertifizierungen
CE
Garantie
Eingeschränkte Garantie für ein Jahr
H WD
96 mm (3.78″) x 96 mm (3.78″) x 132mm (5.20″), 1/4 DIN
Strombedarf
100-240V AC ±10%, 9W max., 50/60 Hz
Gehäuse
NEMA 4X IP65, mit Drucktasten-Bedienfeld
Betriebstemperatur (Umgebung)
0 °C bis 50 °C
Kalibrierungsmodus
Any Tech & NIST-Puffer oder benutzerdefinierte Puffer bis zu 5 Punkten
Ausschnitt im Panel
93mm (3.66″) x 93mm (3.66″)
Analoger Ausgang 1
0/4 -20mA, entsprechend dem pH- oder ORP-Ausgang. Maximale Belastung 500 Ω.
Display
Großes LCD, automatisch gesteuerte Hintergrundbeleuchtung, Text-, Diagramm- oder Spurmodus
Analogausgang 2
0/4 -20mA, entsprechend dem Temperaturausgang. Maximale Belastung 500 Ω
Kontakt
240V AC, 5
240V AC, 30V DC 5.0
Ausgangsspannung
DC +/- 12V, 1W max
A max aktivieren
2 Sollwerte Hoch/Niedrig, Ein/Aus
Montageoptionen
Panel- oder Wandmontage
Abmessungen
11 x 10.5 x 7 in
0-9999 Sekunden /Aus
0-9999 Stunden
Temperaturkompensation
NTC 30K oder Pt1000Ω RTD mit automatischer oder manueller Kompensation
Gewicht
2.27 lbs
Ca. 1.10 lb (0.50 kg)