Our TX3100 is an intelligent pH and ORP controller/transmitter for reading pH and ORP sensors and programmable process control. This controller replaces the TX3000 1/2 DIN pH/ORP controller and features an updated user interface with user friendly full text and graphical display. This makes operation, calibration, and maintenance easier for operators in treatment plants. The TX3100 also features a solution ground input for accurate readings in applications with ground loop issues.
Note: Transmitter is only compatible with sensors with tinned leads.
CA Residents: Prop 65 WARNING(S)
Measurement Range pH: -2.00 to 16.00pH, 0.01 pH resolution
Measurement Range ORP/mV: -1999mV to 1999mV, 1mV resolution, +/- 1mV accuracy
Temperature Range: -30 °C to 130 °C , 0.1 °C resolution, 0.2 °C accuracy
Calibration Mode: Any Tech & NIST or custom buffers up to 3 points
Enclosure: 1/2 DIN NEMA 4X IP65
HWD: 144 mm (3.78″) x 144 mm (3.78″) x 115mm (5.20″)
Panel Cut-Out: 138mm (3.66″) x 138mm (3.66″)
Display: Full graphical and text display
Analog Output 1: 0/4 -20mA, corresponding to pH or ORP output. Max load 500 Ω.
Analog Output 2: 0/4 -20mA, corresponding to temperature output. Max load 500 Ω
Voltage Output: DC +/- 12V, 1W max
Alarm/Control Relays: Contact: 240V AC, 5A max Activate: 2 setpoints Hi/Low, On/Off, Hi/Hi, Low/Low
Wash Setting: Contact: 240V AC, 30V DC 5.0A max On: 0-9999 seconds /Off: 0-9999 hours
Mounting Options: Panel or wall mounting
Ambient Operating Temperature: 0° C to 50° C
Ambient Humidity: 0 to 95%, non-condensing
Temperature Compensation: Pt1000Ω RTD with automatic compensation or manual
Power Requirement: 100-240V AC +/- 10%, 9W max., 50/60 Hz
Warranty: One year limited warranty
Weight: Approx. 1.75lb (0.80kg)
Certifications: CE
| Weight | 2.76 lbs |
|---|---|
| Dimensions | 11 × 10.5 × 6.5 in |
Our TX3100 is an intelligent pH and ORP controller/transmitter for reading pH and ORP sensors and programmable process control. This controller replaces the TX3000 1/2 DIN pH/ORP controller and features an updated user interface with user friendly full text and graphical display. This makes operation, calibration, and maintenance easier for operators in treatment plants. The TX3100 also features a solution ground input for accurate readings in applications with ground loop issues.